In practice, "fire retardant" means a reaction to fire class which the material must be able to prove with documents, for the exact area where you install it. It's not a label on a product on the shelf. The Romanian Fire Safety Standard, P 118/1-2025, requires stricter classes for escape routes than for rooms and adjusts the requirement according to the building. In addition, it prohibits any product that does not have the declared fire performance. For a restaurant, a store, an office, or a clinic, the consequence is simple: the finishes are chosen along with the concept, not after it. Below, you will find the classes explained in simple terms, the requirements by area, the materials by surface and the documents to be checked. If you want these decisions to be made consistently from the very first plan, at SelfDezign we integrate them into the concept, the technical design and the coordination of the execution.

SelfDezign

Integrate fire requirements into the concept

SelfDezign integrates interior concept, technical design and implementation coordination, taking into account the actual objectives of the project.

Visit

In a Nutshell

  • Reaction to fire (Classes A1–F) describes how a material behaves at the start of a fire. Resistance to fire (R, E, I plus minutes, e.g., EI 60) describes how long a wall or ceiling prevents fire from passing from one room to another.
  • A complete class has three parts: the letter, the smoke (s1–s3), and the flaming droplets (d0–d2). Your product must meet the minimum requirements to each of them.
  • On common escape routes, P 118/1-2025 requires from A1 or A2-s1,d0 to at least D-s1,d0, depending on the building's fire resistance level.
  • Products for which the manufacturer declares “no performance determined” (NPD) are prohibited. Without a declared class, the material is not included in the project.
  • As of May 8, 2025, P 118/1-2025 replaced the old P 118-1999. Projects started now are subject to the new standard.

“Fire retardant” means two different things

Many discussions about flame-retardant materials get tangled up from the start because they mix two properties that are not measured in the same way.

Reaction to fire concerns the material itself: whether it ignites, how quickly it contributes to the spread of the flame, how much smoke it produces, and whether it drips while burning. It matters in the first few minutes, while the fire is still confined to a single room. Here we are talking about the finish of a wall, a carpet, wood paneling or a curtain.

Resistance to fire concerns an entire building element: a partition wall, a ceiling, a door. The question is how long that element retains its load-bearing capacity (R), flame and hot gas tightness (E) and thermal insulation (I). That is why it appears written as a combination of letters followed by minutes, for example EI 60. P 118/1-2025 specifies that a higher class includes the lower ones for the same duration: REI includes RE and R, and EI includes E.

The two properties work together, but do not substitute for each other. How does it explain Siniat's guide to fire resistance, a non-load-bearing wall classified as EI 60 does not automatically have the load-bearing performance of REI 60. By way of analogy, the reaction to fire is the "skin" of the space, and the fire resistance is the "skeleton" that keeps the compartments separate. A well-executed interior design concept addresses both, each in its proper place.

„Ignifug” înseamnă două lucruri diferite

Reaction to fire classes, read correctly

In Romania, the classes follow the European classification system, as defined in P 118/1-2025, ch. 1.2 (item 13). In short:

Class

What this means in practice

A1

Non-combustible, does not contribute to fire

A2

Does not ignite with a flame, extremely limited contribution

B

It goes out in the absence of the flame that sustains it, very low intake

H

Contributes to the development of the fire, within certain limits

D

Contributes to the development and spread of fire

E

Significant contribution to rapid spread

F

Very important contribution to propagation

Two indices are added to the basic letter, which often say more about people's safety than the letter itself:

  • s1, s2, s3: the amount of smoke, from little (s1) to much (s3). It is the smoke that reduces visibility along an escape route.
  • d0, d1, d2: burning drops or particles, from none (d0) to many (d2).

Flooring has its own scale, marked with the suffix _FL (from A1_FL to F_FL), with smoke indices s1 or s2. Do not compare a flooring class with a wall class: they are different tests.

The "equal or better" rule, for each component

The standard considers the requirement to be met if the actual performance of the material is equal to or higher than the minimum required. Example from P 118/1-2025, art. 1.1.7: where B-s3,d1 is required, B-s1,d0, A2-s1÷s3,d0÷d1 or A1 are also accepted. The important thing is that the "minimum" applies separately to the letter, smoke and droplets (ch. 1.2, item 12).

A working example: the project requires C-s2,d0 for wall cladding, and the supplier proposes a B-s3,d0 panel. The letter is better, but the smoke (s3) is weaker than s2. The panel does not meet the requirement, no matter how "fireproof" it is presented in the offer. On a construction site, such substitutions seem minor, but at the time of acceptance, they become real problems.

Compararea cerinței C-s2,d0 cu propunerea B-s3,d0

Which class is required, depending on the area

The requirement is not the same for the entire interior. It depends on two things: the area where you install the material and level of fire resistance of the building. This is a classification from I to V. It results from the height and purpose of the building and from the fire performance of the structure's elements (tables 2 and 3 of the standard), and the designer records it in the documentation. Level I is the highest performing.

For finishes on common traffic and escape routes in buildings of normal height, Art. 2.4.6.1 of P 118/1-2025 provides:

Fire stability level

Walls (finishes)

Floors

I II

A1 or A2-s1,d0

A1_FL or A2_FL-s1

III

minimum B-s1,d0

minimum B_FL-s1

IV

minimum C-s1,d0

minimum C_FL-s1

V

minimum D-s1,d0

minimum D_FL-s1

The same article allows room for the finishes that give character to a space. On horizontal escape routes and in rooms, sheets of a maximum of 5 mm glued to an A1 or A2-s1,d0 substrate are allowed. Carpets or wooden floors of up to 20 mm, of at least C_FL-s1, installed directly or on a soundproofing layer, are also allowed. The soundproofing layer must have at least the class required in the table above for the route in question, not just the class of the carpet.

For high-rise buildings, the requirement increases: Art. 4.1.5.11 requires A1 or A2-s1,d0 (i.e., A1_FL or A2_FL-s1) for the walls, ceilings and floors of common escape routes. On corridors and halls, the same article allows films of a maximum of 5 mm, of at least B-s1,d0, glued to an A1 or A2-s1,d0 substrate, and carpets of a maximum of 20 mm, of at least B_FL-s1.

There is a minimum inside rooms as well. Art. 2.4.6.3 requires at least C-s1,d0 (respectively C_FL-s1) for finishes, treatments and insulation in three situations: rooms where people gather in large numbers, any room in a building with more than 50 users, and rooms with healthcare functions. For a large restaurant or a clinic, this is the starting requirement, not the table above.

The table is the starting point, not the final verdict. The purpose of the space (crowded room, healthcare facility, commercial space), the height of the building and the layout change the requirements. The exact class for each area is determined by the fire safety scenario and design, prepared by the specialized designer, and, where required by law, by the ISU approval. You can find details about the approval process in our guide on ISU requirements for interior fittings.

Materials, by surface area

Walls and ceilings

Gypsum is naturally fire-resistant. Siniat explains that gypsum board releases water vapor when exposed to fire. The detail that is often overlooked is another one: reaction to fire class required for gypsum board walls Refers to either: All Components: panels, studs, crossbeams, fasteners and internal insulation. Furthermore, lightweight walls are installed on the basis of technical approvals for systems or European Technical Assessment. In other words, it's the system that matters, not just the board. If you are choosing between a coffered ceiling and a drywall ceiling, the fire criteria are added to the aesthetic and maintenance criteria, which we compared in coffered ceiling vs. drywall.

Wood and wood paneling

Wood remains one of the most expressive materials in a commercial or HoReCa interior. To use it where a higher class is required, it is treated with fire retardant products. The Technical Regulation of October 18, 2011 on fire retardant products for wood and wood-based materials (Ministry of Administration and Interior) requires these products, for interior use, to bring the substrate to Class B or C (with s1–s3 and d0–d1). For the designer, this means that the decision on the treatment is made during the design phase, along with the finish (varnish, oil, paint). The order of application and compatibility are determined according to the technical data sheet of the fire retardant product, not on site.

Floors

The _FL scale matters here. Carpeting and hardwood flooring up to 20 mm are permitted from C_FL-s1 upwards, and the soundproofing layer underneath must be of at least the same class. This is a common specification error: the finish is compliant, but the separately chosen acoustic substrate is not. For areas with heavy traffic and aggressive cleaning, the fire criteria are combined with the wear criteria, which we detail in the guide on durable finishes for HoReCa.

Textiles, upholstery and acoustic panels

Drapes, upholstery and textile acoustic panels add warmth and acoustic comfort. However, they also introduce combustible material into the room. Fire retardant products for textiles appear, along with those for wood, in annex 1 of the Order of the Ministry of Internal Affairs no. 88/2012. The order sets out the certification of technical fire protection means before they are placed on the market. We show how to choose the right acoustic treatment, with the fire class included in the criteria, in the comparison acoustic panels vs. foam.

Films and wallpapers

Decorative films up to 5 mm are accepted on horizontal escape routes and in rooms only when adhered to an A1 or A2-s1,d0 substrate. Basically, the same film can be compliant on a drywall and non-compliant on a combustible cladding.

What to check before ordering and installing

A good material on paper must remain the same on site. These are the checks that matter, in the order in which they appear in a project:

  1. Declaration of performance Search for the complete reaction to fire class, with the letter, s and d. P 118/1-2025 prohibits products for which the manufacturer, importer or distributor declares “no performance determined” (NPD) or “open performance” (OD).
  2. Matching the area. Compare each component of the class with the minimum required for that area. Don't just look at the letter.
  3. The system, not the part. For lightweight walls, request the technical approval or European Technical Assessment of the entire system, including fasteners and insulation.
  4. Labeling of fire retardant products for wood. The 2011 regulation (art. 6) requires labeling in Romanian, including: the trade name, the substrate, the reaction to fire class, the quantity, the batch and the date of manufacture, the manufacturer's details, the shelf life in the packaging and after application, plus the transport and storage conditions.
  5. Certificate for placing on the market. For flame retardant products for wood and textiles, Order 88/2012 provides for a certificate granted for 5 years. The assessment is done by IGSU, through the National Center for Fire Safety and Civil Protection. Products legally marketed in another EU state, in the EEA or in Turkey are exempt. If the product has a certificate, check if it is valid.
  6. Work documents. Keep the technical data sheets, declarations and application documents in the property file. You will need them for the acceptance, for the authorization and for the next renovation.

Most problems do not arise in the design, but between the design and the execution. A supplier proposes an "equally good" equivalent, and a team changes the insulation in a wall. That's why the coordination of execution, which is included in our services, is just as important as the specification.

What has changed in 2025

For over a quarter of a century, the reference has been P 118-1999. According to document sheet on lege5.ro, it was in force between April 7, 1999, and May 8, 2025. On that date, Order 267/2025 (art. 3) ended its applicability. ISU Suceava announced, on the fire safety page of the IGSU site, the entry into force of P 118/1-2025 on May 8, 2025.

Order 267/2025 also contains transitional rules. According to art. 2, the new regulation does not apply to projects that, on the date the order entered into force (May 8, 2025), were in one of these situations:

  • works in progress;
  • public procurement procedures started for the technical project or for the study;
  • technical project, feasibility study or approval documentation received by the investor or submitted for approval or endorsement;
  • technical project drawn up on the basis of a study for which the public procurement had already started;
  • approved technical and economic indicators;
  • financing contract in force;
  • valid urbanism certificate, on the basis of which the approval procedure had started;
  • valid building permit, even if the start of works had not been notified.

If you start a new installation now, you work according to P 118/1-2025. If you take over a space that was started before May 8, 2025, first check with the specialized designer which standard the project remains under.

Our perspective: Fire safety is part of the concept

When we talk about an interior concept, we often describe it as the backbone of the project: the decision that holds together the materials, the lighting, the circulation, and the identity of the space. The reaction to fire class is part of this backbone; it's not a final check.

The difference is evident in the cost and the result. If you choose a wooden floor, a carpet or a curtain just for the ambiance and only then ask what class it belongs to, you end up treating, replacing or getting rid of precisely the elements that gave the space its character. If you ask the question from day one, you usually find the version that preserves both the intention and the compliance.

That's why we start every project from the real context: what kind of building it is, how people move through the space, what the place needs to communicate. In a clinic, finishes must inspire confidence and reduce friction. In a restaurant, they must support the atmosphere and the pace of service. In both cases, the materials must also pass the test that no one wants to see applied.

Toni

How can we help you?

At SelfDezign, we design interiors for commercial spaces, HoReCa, offices, homes and medical clinics: concept, technical design and coordination of on-site implementation. Commercial interior design starts at EUR 25–55/m², and residential interior design starts at EUR 20–40/m². If you already have a space and want clarity on the materials and steps first, consultation with written conclusions costs RON 500 per session. For projects with specific requirements, see also design for HoReCa and design for medical clinics.

Sources

Frequently Asked Questions

Both produce little smoke (s1) and do not drip when burning (d0). The difference is in the contribution to fire: an A2 material does not ignite from a flame and contributes extremely little, while a B material makes a very small contribution. On the escape routes of level I–II buildings, A1 or A2-s1,d0 is required, so B is not enough there.

Yes, as long as it reaches the class required for that area. For interiors, fire retardant products for wood must bring the substrate to class B or C. If the area requires A1 or A2, as happens on the escape routes of level I–II buildings, treated wood does not get there, so its place in the concept is chosen accordingly.

The manufacturer must state on the label how long the product stays valid after application. Note this period in the space file and plan the reapplication in good time, especially before inspections or re-authorizations.

It depends on the stage it was at on May 8, 2025, the date the order entered into force. Works in progress, documentation submitted for approval or building permits valid on that date usually stay under the old rules, under the transitional rules of Order 267/2025. Confirm the classification with the fire safety designer before you order materials.